Detailed description - ERV-08M time relay (0.1 s - 100 h), Un: 12-230 V AC/DC
The ERV-08M time relay is a universal delay relay designed to control delayed activation after power supply voltage is applied. It offers a wide time range from 0.1 seconds to 100 hours, universal power supply 12-230 V AC/DC, simple control, and DIN rail mounting.
Suitable for automation applications, controlling fans, motors, lighting, contactors, and other devices requiring delayed activation.
Main features
-
Function of delayed start of the NO contact when voltage is applied
-
Wide time range: from 0.1 s to 100 h
-
Universal power supply: 12-230 V AC/DC (4 VA)
-
1× SPDT changeover contact ( NO/NC), 5A/250VAC
-
Two LED indicators:
-
ON (red) - power present
-
OUT (green) - output relay status
-
-
Time setting with two rotary potentiometers
-
Mounting on 35 mm DIN rail
-
Protection IP20
-
Compact dimensions: 91 × 18 × 65 mm
Control and functions
LED indication
-
ON (red) - relay is powered
-
OUT (green, steady on) - output relay is energized (contact 2-3 connected)
-
OUT (green, blinking) - countdown to switching is in progress
Time setting
The time relay allows you to create an accurate delay with two potentiometers:
-
Potentiometer "t" (0.1 to 10)
- precise adjustment in % of the total range
- 0.1 = 1 %, 10 = 100 %. -
Potentiometer "TS" - range selection:
-
A = 10 s
-
B = 100 s
-
C = 10 min
-
D = 100 min
-
E = 10 h
-
F = 100 h
-
Time change activates on the next power connection.
Switching function
1) ON Delay - delayed activation (terminals 2-3, NO)
-
When power is connected, the set time countdown begins
-
After the elapsed time, the output relay (RLY) is activated - contact 2-3 (NO → COM) closes
2) Off delay via NC contact (terminals 2-1)
-
Contact 2-1 (NC) is active even without power
-
When power is connected, the countdown begins
-
After the elapsed time, the contacts 1-2 open
Usage
The ERV-08M time relay is used for applications requiring a delayed load activation after an event occurs:
-
The fan turns on only after the light is switched on (toilet, bathroom)
-
Lighting in the garage or hallway after door opening
-
Gradual motor start-up
-
Delayed switching of contactors
-
Sequential switching of multiple circuits
-
delayed device activation
The timing starts when the relay is connected to power.
Online payment by card - after completing the order you will be redirected to the payment gateway, payment confirmation will be sent to your e-mail
COD - you pay the payment by money order to the carrier's driver
By bank transfer - no later than the next working day, you will receive an advance invoice to your e-mail, which contains the account number that you will enter when making the payment.
On pro forma invoice - this payment option is available to partners who have signed a framework agreement with our company.
If you want to use the last 2 methods, please call our manager and he will give you instructions on how to receive an invoice with or without VAT.
The electrical equipment we supply meets high quality standards, has a 24-month warranty, and meets all EU requirements.
In the event of a complaint, the return of goods will not be charged.