Temperature and humidity controller HT-310 TENSE
Product description
Relay for temperature and humidity control. The temperature and humidity regulator has separate outputs, hysteresis adjustment, and is designed for wall mounting. Device dimensions: 72 × 36 × 100 mm.
This controller is suitable for controlling air conditioning devices, heating systems, dehumidification, heating, and other processes where temperature and humidity need to be measured and controlled.
Main features
-
Sensor type: NT-310 (common for temperature and humidity)
-
Temperature measurement range: -19.9 °C ... +80.0 °C; step 1 °C
-
Humidity measurement range: 5 % ... 95 %; step 1
-
Control principle: ON-OFF
-
Outputs:
-
°C OUT: changeover control contact, 2 A resistive load for temperature
-
%RH OUT: normally open contact, 2 A resistive load for humidity
-
-
Operating modes:
-
Temperature: cooling/heating
-
Humidity: dehumidification / humidification
-
-
Hysteresis: separately adjustable for temperature and humidity
-
ALARM: choice between absolute, relative temperature or sensor error
-
On/off delay: for cooling mode (e.g., compressors)
-
Fixed offset: adjustable for temperature or humidity when sensor wire length changes
-
Password protection: security of set parameters
-
Memory: non-volatile EEPROM memory for storing settings
-
Connection: easy disconnect/connection to the controlled device with quick connectors
-
Power supply: 100-240 V, 50-60 Hz
Usage
The controller can be used as:
-
Humidistat / hygrometer / humidity meter / density meter (hygrometer)
-
thermostat / thermal relay
-
Relay for measuring humidity and air temperature levels
Safety warning
-
When connecting the temperature sensor, observe polarity, as incorrect connections can cause sensor damage or improper controller operation.
-
When connecting the controller to the power supply, use a fuse of 250 mA/250 V and cables of appropriate cross-section.
-
Observe electrical safety rules.
-
Use shielded grounded wire in the form of a twisted pair for signal contacts. Install cables away from electrical wiring, contactors, and electromagnetic fields.
-
Important: The device must be installed in an environment with a temperature of -20...+55 °C, otherwise the plastic housing may deform and the controller may fail.
Online payment by card - after completing the order you will be redirected to the payment gateway, payment confirmation will be sent to your e-mail
COD - you pay the payment by money order to the carrier's driver
By bank transfer - no later than the next working day, you will receive an advance invoice to your e-mail, which contains the account number that you will enter when making the payment.
On pro forma invoice - this payment option is available to partners who have signed a framework agreement with our company.
If you want to use the last 2 methods, please call our manager and he will give you instructions on how to receive an invoice with or without VAT.
The electrical equipment we supply meets high quality standards, has a 24-month warranty, and meets all EU requirements.
In the event of a complaint, the return of goods will not be charged.